KA-S15B 86 Dual Tech Dual Technology Ultrasonic and PIR Wall Mount Occupancy Sensor specifications:
1. Voltage: 120/277VAC,50/60Hz
2. Load Requirments: Incandescent....800W-120VAC,50/60Hz
Fluorescent....800VA-120VAC,1600VA-277VAC,50/60Hz
Motor ..... 1/4HP-120VAC,50/60Hz
3. Adjustment Time Delay: 15Sec to 30Mins
4. Walk-Through Mode: 3 minutes if no activity after 30 sec.
5. Test Mode: 15 sec. at initial power up or DIP switch reset
6. PIR Adjustment: High or Low (DIP switch)
7. Ultrasonic Adjustment: Minimum to Maximum (trimpot)
8. Light Level Adjustment: 100 Lux --daylight(trimpot)
9. Operation Temperature: 32° F--131° F
Product Description:
This Multi-Technology Wall Switch Sensor combine advanced passive
infrared (PIR) and ultrasonic technologies into one unit. The combined technologies help to avoid false triggering.Selectable operating modes
allow the sensor to turn a load on, and hold it on as long as either or both technologies detect occupancy . After no movement is detected
for the selected time delay, the lights switch off. A "walk-through"mode can turn lights off after only 3 minutes,
if no activity is detected after 30 seconds following an occupancy detection.This sensor also contains a light level sensor. If adequate daylight
is present, the sensor holds the load OFF until light levels drop, even if the area is occupied.
KA-S15B Operations:
The Sensor Switch is programmed independently for either Occupancy Mode or Vacancy Mode as refer to the Band Switch position under the
control panel cover. Some might call the Vacancy mode as "Manual On Occupancy Mode".
Manual On/Off Button
By Pushing the Control Panel Cover, the Load can be turned On/Off under either OCC or VAC mode.
Turning On the Load under Occupancy Mode
Load to be Automatic On once occupancy detected.
Turning On the Load under Vacancy Mode
Manual On/Off Button has to be pushed to turn On the Load.
Automatic Turning Off the Load
Under either mode, the Sensor keeps the Load On until no motion is
detected plus the set time delay, load(s) to be Off automatically.
Under VAC Mode, the Load can turn On automatically if motion detected
within the first 3 minutes.
Manual Turning Off the Load
By Manual On/Off Button, the Load can be turned Off under either OCC or VAC mode.
Under OCC Mode, if you press manual On/Off button first,when set-time is more than 3 minutes, the sensor switch returns to normal
after 3 minutes. However, when set-time is less than 3 minutes,the sensor switch returns to normal until set-time finished.
Note: Only when there is no motion is detected during the set-time
period, the sensor switch returns to normal.
Ultrasonic Sensitivity Adjustment Trimpot
Default position: Center at 65% Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source.